Item number: Z463C

Flexible 3-Phase Current Sensor 60/600/6000 AAC, Loop Length 61... 122 cm

  • Flexible 3-Phase Current Sensor 60/600/6000 AAC, Loop Length 61... 122 cm

The flexible 3-phase current sensor is used in combination with MAVOWATT 30, 40, 70 or any measuring instruments of up to 1,5 V AC measuring input and Hypertronics plug.

The flexible current transformers can be placed around one or several conductors of any type and design (insulated cable, busbars, pipes).

Internal batteries allow for an independent operation of the measuring amplifier.

  • Technical characteristics
    • CAT III 1000 V
    • Wide range of applications, 3 measuring ranges 60 /600 /6000 A AC and large bandwidth 10 Hz ... 10 kHz for harmonic analysis
    • Simultaneous measurement in all 3 phases
    • Precise measurements even with low currents, due to wide dynamic range and high sensor sensitivity
    • Low conductor position influence and minimum stray field influence
    • Easy to operate in restricted space thanks to small sensor cross-section of 9.9 mm and slim end cap of 13.6 mm
    • Safe handling even with protection gloves; opening of sensor and measuring range setting in one-hand operation
    • Extremely long battery life of up to 1,000 hours
    • External power supply for long-term measurements (optional)
    • Current sensor with protection type IP65, measuring amplifier with IP40
    • High level of safety for the user, measurement category 1000 V@CATIII, 600 V@CATIV and unlimited overload capacity

    Feature Specifications

    Measuring ranges 60 A 600 A 6000 A

    Output signal (AC) 50 mV/A 5 mV/A 0,5 mV/A

    Residual current / ripple 8 mV eff. 2 mV eff. 2 mV eff.

    Measuring uncertainty (45... 65 Hz) ±1% ±0,1 A ±1% ±0,1 A ±1% ±1 A

    Overload capacity unlimited

    Linearity ±0,2% of rdg.

    Bandwidth 10 Hz bis 10 kHz (-1 dB)

    Phase angle error < ±1° (45... 65 Hz)

    Min. load impedance 100 kO for indicated accuracy

Accessory for the following Products

Contact

Do you have any questions on the product or do you need technical information or details on the current delivery period? Our sales backoffice will be pleased to assist you.

Sales International:
Telephone: +49 911 8602-0
Send message

myGMC

Under myGMC you can register your product and receive up-to-date information on firmware updates, modifications of standards and many more topics.

Dialogue, Information and Actions: