| METRAHIT ENERGY | |
|---|---|
| Item number | M249A |
| Product details page | Details |
| Display | |
| Indication | Digital |
| Indication digits | 60000 |
| Multiple display | x |
| Measuring range selection | Manual/automatic |
| Basic data | |
| Type of measurement | TRMS |
| True RMS measurement | x |
| Basic accuracy | 0.02Percentage |
| Measuring circuit category | CAT IV |
| Max. voltage measuring circuit category | 300Volt |
| Relative value measurement | x |
| Min. value storage | x |
| Max. value storage | x |
| Peak value memory | x |
| Data hold | x |
| Special functions | |
| Explosion-tested version | |
| Power and energy measurement | x |
| Harmonics analysis/power quality | x |
| Crest factor measurement | x |
| Rotational speed measuring | |
| Duty cycle measurements | x |
| Pulse freqency measurement MHz @ 5V TTL | x |
| Inductance measurement | |
| Interturn short-circuit high-voltage test | |
| Automatic circuit breaker | |
| Voltage measurement | |
| Voltage measurement types |
DC AC AC Fil AC+DC |
| With decibel measurement (dB) | x |
| Voltage measuring range DC | 0,000001Volt - 600Volt |
| Voltage measuring ranges DC |
60 mV 600 mV 6 V 60 V 600 V |
| Max. voltage measuring range, DC | 600Volt |
| Lowest resolution, DC voltage | 0.001 mV |
| Internal resistance volt DC | 17 |
| Voltage measuring range AC | 0,00001Volt - 600Volt |
| Voltage measuring ranges AC |
600 mV 6 V 60 V 600 V |
| Max. voltage measuring range, AC | 600Volt |
| Lowest resolution, AC voltage | 0.01 mV |
| Frequency range volt AC | 15Hertz - 100000Hertz |
| Internal resistance volt AC | 9 |
| Low-pass filter AC voltage (fc) | 1kiloHertz |
| Voltage measuring range AC+DC | 0,00001Volt - 600Volt |
| Voltage measuring ranges AC+DC |
600 mV 6 V 60 V 600 V |
| Max. voltage measuring range, AC+DC | 600Volt |
| Lowest resolution volt AC+DC | 0.01Millivolt |
| Internal resistance volt AC+DC | 9 |
| Frequency range volt AC+DC | 100kiloHertz |
| Level measurement voltage types | AC |
| Measuring range voltage level for U ref = 0.775 V | -48Decibel - 58Decibel |
| Lowest resolution voltage level | 0.01Decibel |
| Current measurement | |
| Current measurement types |
DC AC AC+DC |
| Current measurement range DC | 0,00000001Ampere - 10Ampere |
| Current measuring ranges DC |
600µA 6 mA 60 mA 600 mA 6:00 AM 10:00 AM |
| Max. current measuring range, DC | 10Ampere |
| Lowest resolution, DC current | 0.01 µA |
| Current measurement range AC | 0,00000001Ampere - 10Ampere |
| Current measuring ranges AC |
600µA 6 mA 60 mA 600 mA 6:00 AM 10:00 AM |
| Max. current measuring range, AC | 10Ampere |
| Lowest resolution, AC current | 0.01 µA |
| Frequency range alternating current | 15Hertz - 10000Hertz |
| Current measurement range AC+DC | 0,00000001Ampere - 10Ampere |
| Current measuring ranges AC+DC |
600µA 6 mA 60 mA 600 mA 6 A 10:00 AM |
| Max. current measuring range AC + DC | 10Ampere |
| Lowest resolution amps AC+DC | 0,00001Milliampere |
| Frequency range amps AC+DC | 10kiloHertz |
| Current sensor with clipping | x |
| Current measuring range with current sensors | 0,00001Ampere - 60000Ampere |
| Current transformer with clipping | x |
| Current measuring range with current transformers | 0,000001Ampere - 6000Ampere |
| Clip factors |
01:01 01:10 0,111111111 0,736111111 |
| Resistance measurement | |
| Milliohm measurement with 4 wire technique (Kelvin connection) | |
| Resistance test/diode test | x |
| Continuity test | x |
| With conductivity measurement | x |
| Resistance measurement range | 0.01Ohm - 60000Ohm |
| Resistance measurement ranges |
600 6 k 60 k 600 k 6 M 60 m |
| Max. resistance measuring range | 60Mega-Ohm |
| Lowest resolution, resistance | 0.01 Ohm |
| Lowest resolution, milliohm measurement | 10Milli-Ohm |
| Nominal test voltage 10 V | |
| Nominal test voltage 50 V | |
| Nominal test voltage 100 V | |
| Nominal test voltage 250 V | |
| Nominal test voltage 500 V | |
| Nominal test voltage 1000 V | |
| Capacitance measurement | |
| Capacitance measurement | x |
| Capacitance measuring range | 0,00001Mikro-Farad - 600Mikro-Farad |
| Capacitance measurement ranges |
60 nF 600 nF 6 �F 60 �F 600µF |
| Max. capacitance measuring range | 600Mikro-Farad |
| Lowest resolution, capacitance | 0.00001 µF |
| Cable length measurement | x |
| Cable symmetry testing for two wire connections a-b-E | |
| Frequency measurement | |
| Frequency measurement | x |
| Measuring range for frequency | 0,00001kiloHertz - 1000kiloHertz |
| Max. frequency measuring range | 1000kiloHertz |
| Lowest resolution, frequency | 0.01 Hz |
| Temperature measurement | |
| Temperature measurement | x |
| Temperature measurement TC | x |
| Temperature measuring range TC | -250Degrees celsius - 1372Degrees celsius |
| Temperature measurement RTD | x |
| Temperature measuring range RTD | -200Degrees celsius - 850Degrees celsius |
| Max. temperature measuring range | 1372Degrees celsius |
| Lowest resolution temperature | 0.1 °C |
| Interface and memory | |
| Interface | x |
| Bluetooth interface | |
| IR interface | x |
| Measured value memory | x |
| Memory capacity for measured values | 300000 |
| Miscellaneous | |
| Power supply unit socket | x |