Item number: Z525A

Test adapter for electric charging stations (single/3-phase, type 2) for PROFITEST

Single and 3-phase test adapter with type 2 plug for testing the effectiveness of protective measures at electric charging stations with the Profitest Master, simulation of fictitiously connected electric vehicles and current-carrying capacity of cord sets per IEC 61851-1
  • Test adapter for electric charging stations (single/3-phase, type 2) for PROFITEST
  • Test adapter for electric charging stations (single/3-phase, type 2) for PROFITEST

  • Vehicle simulation (CP)
    Vehicle states A through E are selected with a rotary switch.
  • Cable simulation (PP)
    The various codings for charging cables with 13, 20, 32 and 63 A, as well as “no cable connected”, can be simulated with the help of a rotary switch.
  • Fault simulation
    simulation of a short-circuit between CP and PE by means of a rotary switch
  • Indication of phase voltages via LEDs
    Depending on the charging station, either one or three phases can be active.
  • Testing of electric charging stations with permanently attached charging cable by means of an extended CP test pin

  • Technical characteristics

    For vehicle simulation (CP)
    States A, B, C, D and E can be simulated in accordance with IEC 61851. The various vehicle states are selected by means of a rotary switch.

    • State A – no vehicle connected
    • State B – vehicle connected, but not ready for charging
    • State C – vehicle connected and ready for charging, venting of the charging area not required
    • State D – vehicle connected and ready for charging, venting of the charging area required
    • State E – error: Short circuit between CP and PE via internal diode

    Regarding cable simulation (PP):
    The various codings for charging cables with 13, 20, 32 and 63 A can be simulated. It’s also possible to simulate the “no cable” state.

    The various charging cables are simulated by connecting different resistances between PP and PE with the help of a rotary switch. The following values are possible in accordance with IEC 61851:

    • No cable – 0 Ω
    • 13 A cable – 1.5 kΩ
    • 20 A cable – 680 Ω
    • 32 A cable – 220 Ω
    • 63 A cable – 100 Ω

Accessories

Accessory for the following Products

Contact

Do you have any questions on the product or do you need technical information or details on the current delivery period? Our sales backoffice will be pleased to assist you.

Sales International:
Telephone: +49 911 8602-0
Send message

myGMC

Under myGMC you can register your product and receive up-to-date information on firmware updates, modifications of standards and many more topics.

Dialogue, Information and Actions: