Options
In field housing without display or with TFT display
Communication
- Ethernet (Modbus/TCP, http/https, NTP, SFTP, SYSLOG, REST API)
- Modbus/RTU
- Optional: IEC61850, MQTT (planned for 2025)
- Automated data export (CSV and PQDIF files) to SFTP server
Cyber Security (OT) / Cyber Protection
- Role-based access authorization (RBAC)
- Hypertext Transfer Protocol Secure (https)
- Client Whitelist / Client IEC61850 Whitelist [Firewall]
- Audit log [registration of all manipulations]
- Sys-Log
- Secure firmware updates
- Data export
Further properties
- Metrologically certified PQI according to IEC 61000-4-30 Ed. 3 class A as basic device
- A scalable system for certified power quality as well as load and efficiency management for up to 10 channels (32 conductors)
- Monitoring of outgoing circuits with 3 or 4 currents with 3P/3PN Current Link modules (max. 32 currents)
- Simultaneous measurement of multiple outlets instead of traditional per-outlet measurement
- Direct conformity reporting and event display through PQEasy reporting via web browser (e.g. in accordance with EN 50160)
- Fault recording of voltage events, optionally with the time-synchronized currents of the reference channel
- Time-synchronized load management for U/I/P/Q/PF
- Current measurement per current link channel “IN1 (typical/maximum) of 400 A / 1,000 A” and “IN2 (typical/maximum) of 8,000 A / 20,000 A”
- Grid tariff meter P & Q (supply & demand)
- System management via a user-friendly multi-device tool for simple commissioning and efficient maintenance
- Low space requirement & low wiring effort based on the scalable current sensors
- It is not necessary to shut down the system to install the measuring system due to the non-invasive Rogowski measuring technology
- Very high robustness due to proven coaxial principle
- Current values are time-synchronized with the voltage (IEC 61000-4-30)
- Open communication system enables high connection flexibility to both parallel and higher-level systems
- Very fast installation with robust measurement technology
- Sampling rate of the currents 54 kHz
Test report
- Included in the scope of delivery
Data analysis
The free PQDiffractor software from Electrotek Concepts can be downloaded via the link http://www.pqview.com/pqdiffractor/ (registration required). With this software, the data from the PQDIF files can be analyzed, saved in CSV format or exported as a graphic.
Digital network management
SMARTCOLLECT® SC2 software can be used to set up a complete ecosystem for power quality and power monitoring.